• ATS1-100/3P A
  • ATS1 series dual power automatic transfer switch is belong to CB grade automatic transfer switch if you choose the breaker with over-current trip as actuator. It is with selective protection function, and provide short-circuit and overload protection to the load and cables at bottom.Its ability of closing and breaking circuit is far more larger than use of contactors and relays , and other components.
    Usage category:AC-33B
    Anti-heat&humidity measure have passed the test under stringent environmental conditions, the standards are as follows:
    IEC 60068-2-1 Dry and cold environment(-25℃)
    IEC 60068-2-1 Dry and hot environment(+70℃)
    IEC 60068-2-1 Low terperature
    45℃时, Use under 95%Relative humidity of the environment
    55℃时, Use under 80%Relative humidity of the environment
    EMC Electromagnetic compatibility
    ATS1 Automatic transfer switch can resist
    electrostatic discharge(IEC 61000-4-2)Level 2
    Radio frequency electromagnetic radiation immunity(IEC 61000-4-2)Level 3
    Electrical transient burst fast(IEC 61000-4-2)Level 3
    Surge(IEC 61000-4-2)Level 4
    Radio frequency electromagnetic conduction immunity(IEC 61000-4-2)Level 3
    Radiation level(CISPR11) B Class

    Standards: IEC60947-1,IEC60947-2,IEC60947-6-1,GB14048.1General rules,GB14048.2 Breaker
    GB14048.11Automatic transfer switch
  • Frame Current Level: 100A, 160A, 250A

    Pole2/3/4P

    Controller TypeB Board typeB Device type

    Electric level: CB with short circuit and overload protection

    Working modeR self-input and self back to normalS self-input not back to normal I Mutual reserve

  • Copyright © 2005-2015 Zhejiang Zoroad Electric Co. Ltd. All Rights Reserved.